1.Enter Inner pipe diameter (Di) Menu 2.1.2.9
输入管道内径
2. Enter Supported paths for inline systems Menu2.1.6.1
选择Path1保存 (选择通道,默认选择通道1,实际根据变送器通道使用情况)
3. Enter Beam angle Menu 2.1.6.2
选择角度45°或60° (输入换能器与管道的安装角度,菜单可能显示rad,弧度。1.05rad=60°)
4. Enter Path length (L1) Menu 2.1.6.3.3
输入通道长度
5. Enter Chord height ratio (h1) Menu 2.1.6.3.4
输入:0
6. Enter Path 1 weight Menu 2.1.6.3.5
输入:1
7. Verify the Pre-amplifier Setting Menu 2.1.13.1
Below you will find the sensor sizes and the corresponding settings.
DN150 – DN1000 = off
DN1000 and bigger = on
DN50 – DN150 = Half TX signal amplitude